NESC & NEC Cross-Code Correlation

Loading
loading...

NESC & NEC Cross-Code Correlation

May 15, 2024
mike@standardsmichigan.com

No Comments

Statement from NARUC During its Summer 2018 Committee Meetings

IEEE Education & Healthcare Facilities Committee

Draft Proposals for the 2028 National Electrical Safety Code

Representative State Level Service Quality Standards

MI Power Grid

Relevant Research


PROCESS, PROCEDURES & SCHEDULE

Mike Anthony is ID Number 469 | Proposal period closes 11:59 PM US Pacific Time | May 15

Meeting Notes in red

Loss of electric power and internet service happens more frequently and poses at least an equal — if not greater threat — to public safety.  So why does neither the National Electrical Code or the National Electrical Safety Code integrate reliability into their core requirements?  Reliability requirements appear in a network of related documents, either referenced, or incorporated by reference; sometimes automatically, sometimes not.

NESC Main Committee Membership: Page xii

Apart from the IEEE as the accredited standards developer, there are no “pure non-government user-interests” on this committee; although ANSI’s Essential Requirements for balance of interests provides highly nuanced interpretation.  The Classifications on Page xiii represents due diligence on meeting balance of interest requirements.

In our case, we are one of many large universities that usually own district energy plants that both generate and purchase generate electric power (as sometimes provide var support to utilities when necessary; as during the August 2003 North American outage).  For University of Michigan, for example, has about 20 service points at 4.8 – 120 kV.  Its Central Power Plant is the largest cogeneration plant on the DTE system.

Contents: Page xxviii | PDF Page 29

Absence of internet service is at least as much a hazard, and more frequent, than downed wires.   Is there a standards solution?  Consideration of interoperability of internet service power supported on utility poles  should track in the next revision.

No mention of any reliability related IEEE reliability standards in the present edition.  Why is this?

Section 2: Definitions of Special Terms | PDF Page 46

In the 2023 Handbook, the term “reliability” shows up 34 times.

availability (from Bob Arno’s IEEE 3006-series and IEEE 493 Gold Book revision)

reliability (Bob Arno)

utility (PDF Page 57)

communication | PDF Page 47

list of terms defined in the 2023 National Electrical Code that are new and relevant to this revision: (Article 100 NEC)

Bonding jumper, system and supply

Survivability of communication network signaling

Fiber optic cable mounted on common poles with a medium voltage overhead line standardizing procedure

municipal broadband network, digital subscriber line, surveillance cameras

wireless communication system

010. Purpose | PDF Page 40

Looks like improvement since last edition.  Suggest explicit Informational Note, as in the NEC, using “reliability” and referring to other agencies.  “Abnormal events” could be tighter and refer to other standards for abnormal, steady-state events.   The clarification of purpose is welcomed although a great deal remains uncovered by other best practice literature; though that can be repaired in this edition.

Legacy of shared circuit path standards. Should provisions be made for municipal surveillance, traffic and vehicle control infrastructure.  What would that look like?

011. Scope | Covered PDF Page 40

3. Utility facilities and functions of utilities that either (a) generate energy by conversion from
some other form of energy such as, but not limited to, fossil fuel, chemical, electrochemical,
nuclear, solar, mechanical, wind or hydraulic or communication signals, or accept energy or
communication signals from another entity, or (b) provide that energy or communication
signals through a delivery point to another entity.

5. Utility facilities and functions on the line side of the service point supplied by underground or
overhead conductors maintained and/or installed under exclusive control of utilities located on
public or private property in accordance with legally established easements or rights-of-way,
contracts, other agreements (written or by conditions of service), or as authorized by a
regulating or controlling body.
NOTE: Agreements to locate utility facilities on property may be required where easements are either
(a) not obtainable (such as locating utility facilities on existing rights-of-way of railroads or other entities,
military bases, federal lands, Native American reservations, lands controlled by a port authority, or other
governmental agency), or (b) not necessary (such as locating facilities necessary for requested service to a
site).

012. General Rules | Covered PDF Page 42

For all particulars not specified, but within the scope of these rules, as stated in Rule 011A, design,
construction, operation, and maintenance should be done in accordance with accepted good practice
for the given local conditions known at the time by those responsible for the communication or
supply lines and equipment

General purpose clause could use some work since no definition of “accepted good practice”.  Refer to IEEE bibliography.

 

Section 2: Definition of special terms | PDF Page 46

Recommendations elsewhere should track here.

 The word “installation” appears 256 times and is generally understood in context by experts.  Suggest borrow from NEC to clarify our concern for including co-linear/communication circuits. 

conduit.  exclusive control, lines, photovoltaic, NEC interactive. qualified

Section 3: Reference

NFPA 70®, National Electrical Code® (NEC®). [Rules 011B4 NOTE, 099C NOTE 1, and 127

IEEE Std 4™-1995, IEEE Standard Techniques for High-Voltage Testing. [Table 410-2 and Table 410-3]
IEEE Std 516™-2009, IEEE Guide for Maintenance Methods on Energized Power-Lines. [Rules 441A4
NOTE 2, 446B1, and 446D3 NOTE, and Table 441-5, Footnote 4]
IEEE Std 1427™-2006, IEEE Guide for Recommended Electrical Clearances and Insulation Levels in
Air-Insulated Electrical Power Substations. [Rule 124A1 NOTE, Table 124-1, 176 NOTE, and 177 NOTE]
IEEE Std 1584™-2002, IEEE Guide for Performing Arc Flash Hazard Calculations. [Table 410-1,
Footnotes 1, 3, 6, and 14]
IEEE Std C62.82.1™-2010, IEEE Standard for Insulation Coordination—Definitions, Principles, and Rules.
[Table 124-1 Footnote 5]

Add references to Gold Book, 1386, etc. IEC since multinationals conform.

 

Safety Rules for the Installation and Maintenance of Overhead Electric Supply and Communication Line | PDF Page 111

Has anyone confirmed that these tables match NEC Table 495.24 lately?  If it helps: there were no meaningful changes in the 2023 NEC in Article 495, the high voltage article

Section 11. Protective arrangements in electric supply stations | PDF Page 77

A safety sign shall be displayed on or beside the door or gate at each entrance. For fenced or
walled electric supply stations without roofs, a safety sign shall be displayed on each exterior
side of the fenced or wall enclosure. Where the station is entirely enclosed by walls and roof, a
safety sign is required only at ground level entrances. Where entrance is gained through
sequential doors, the safety sign should be located at the inner door position.  (A clarification but no change.  See Standards Michigan 2017 proposals)

Recommend that all oil-filled cans be removed and services upgraded through energy regulations with new kVA ratings

Section 12: Installation and maintenance of equipment

093. Grounding conductor and means of connection

Fences
The grounding conductor for fences required to be effectively grounded by other parts of this
Code shall meet the requirements of Rule 093C5 or shall be steel wire not smaller than Stl WG
No. 5.

D. Guarding and protection | PDF Page 67

124. Guarding live parts| PDF Page 85

Propose roofs required for exterior installations

Part 2. Safety Rules for the Installation and Maintenance of Overhead Electric Supply and Communication Line | Page 72

Section 22. Relations between various classes of lines and equipment | Page 80

222. Joint use of structures | Page 82

Where the practice of joint use is mutually agreed upon by the affected utilities, facilities shall be subject to the appropriate grade of construction specified in Section 24. Joint use of structures should be
considered for circuits along highways, roads, streets, and alleys. The choice between joint use of structures and separate lines shall be determined through cooperative consideration with other joint
users of all the factors involved, including the character of circuits, worker safety, the total number and weight of conductors, tree conditions, number and location of branches and service drops, structure
conflicts, availability of right-of-way, etc.

Reliability considerations for sustaining internet service when power supply is absent. 

Par2 Section 20 Safety Rules for the Installation and Maintenance of Overhead Electric Supply and Communication Line | PDF Page 111

Has anyone confirmed that these tables match NEC Table 495.24 lately?

Part 3. Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines | Page 220

Renewable energy for internet access

311. Installation and maintenance

A. Persons responsible for underground facilities shall be able to indicate the location of their facilities.
B. Reasonable advance notice should be given to owners or operators of other proximate facilities that
may be adversely affected by new construction or changes in existing facilities.
C. For emergency installations, supply and communication cables may be laid directly on grade if the
cables do not unreasonably obstruct pedestrian or vehicular traffic and either:

1. The cables are covered, enclosed, or otherwise protected, or
2. The locations of the cables are conspicuous.
Supply cables operating above 600 V shall meet either Rule 230C or 350B.
NOTE: See Rules 014B2 and 230A2d.

Part 4. Work Rules for the Operation of Electric Supply and Communications Lines and Equipment | PDF Page 289

When and why was the term “Work” added to the title of this section?   

Core text for the definition of wireless communication system reliability

 


Appendix E Bibliography| PDF Page 355

 

 

 

Index | PDF Page 398

 


The word “reliability” appears only three times.  Should it track in the NESC or should it track in individual state requirements.  So neither the NEC nor the NESC couples closely with power and communication reliability; despite the enormity and speed of research.

 

Grandma’s Chicken Soup

May 14, 2024
mike@standardsmichigan.com

No Comments

Nebraska

WRITTEN BY Kalani Simpson PUBLISHED May 25, 2021

 

Ingredients:

  • 1 5- to 6-pound stewing hen or baking chicken
  • 1 package of chicken wings
  • 3 large onions
  • 1 large sweet potato
  • 3 parsnips
  • 2 turnips
  • 11 to 12 large carrots
  • 5 to 6 celery stems
  • 1 bunch of parsley
  • Salt and pepper to taste

Directions:

  1. Clean the chicken, put it in a large pot and cover it with cold water. Bring the water to boil.
  2. Add the chicken wings, onions, sweet potato, parsnips, turnips and carrots. Boil about 1 and a half hours. Remove fat from the surface as it accumulates.
  3. Add the parsley and celery. Cook the mixture about 45 min. longer.
  4. Remove the chicken. The chicken is not used further for the soup. (The meat makes excellent chicken parmesan.)
  5. Put the vegetables in a food processor until they are chopped fine or pass through a strainer. Both were performed in the present study.
  6. Add salt and pepper to taste.

(Note: This soup freezes well.)  Matzo balls were prepared according to the recipe on the back of the box of matzo meal (Manischewitz).

PRINT Recipe

b

 

Illumination 300

May 14, 2024
mike@standardsmichigan.com
No Comments

“Starry Night Over the Rhône” 1888 Vincent van Gogh

Today we refresh our understanding of the moment in illumination technologies for outdoor lighting systems— related but different from our exploration of building interior illumination systems in Illumination 200.  Later in 2023 we will roll out Illumination 500 which explores litigation related to public illumination technology.  As cities-within-cities the shared perimeter of a campus with the host municipality has proven rich in legal controversy and action.

Illumination technology was the original inspiration for the electric utility industry; providing night-time security and transforming every sector of every economy on earth.  Lighting load remains the largest component of any building’s electric load — about 35 percent– making it a large target for energy regulations.

Our inquiry begins with selections from the following documents…

International Electrotechnical Commission TC 34 Lighting

IEC 60364 Electrical Installations in Buildings

2023 National Electrical Safety Code

IEEE P3001.9 – Recommended Practice for the Design of Power Systems Supplying Lighting Systems in Commercial and Industrial Facilities (under development)

Institution of Engineering and Technology: Recommendations for Energy-efficient Exterior Lighting Systems

2020 National Electrical Code: Article 410  (While the bulk of the NEC concerns indoor wiring fire hazards, there are passages that inform outdoor lighting wiring safety)

2019 ASHRAE 90.1: Chapter 9 Lighting

Illumination Engineering Society: Various titles

ISO/TC 274 Light and lighting

Salt Water River Project: Outdoor Lighting Standards

…and about 20 other accredited, consortia or ad hoc standards developers and publishers aligned principally with vertical incumbents.  Illumination was the original inspiration (i.e. the first “killer app”) for the electrical power industry in every nation.  Its best practice literature reflects a fast-moving, shape-changing domain.

Click in today with the login credentials at the upper right of our home page.

Upper Wharfedale Primary Federation School District Yorkshire Dales

McGill University: Before electricity, streets were filled with gas lights

Outdoor lighting systems can be owned and maintained by different entities depending on the context and location. Here are some examples of ownership regimes for outdoor lighting systems:

  1. Public ownership: In this case, outdoor lighting systems are owned and maintained by the local government or municipal authority. The lighting may be installed in public spaces such as parks, streets, and other outdoor areas for the safety and convenience of the public.
  2. Private ownership: Outdoor lighting systems may be owned by private individuals or organizations. For example, a business owner may install outdoor lighting for security or aesthetic reasons, or a homeowner may install outdoor lighting in their garden or yard.
  3. Co-owned: Outdoor lighting systems may be owned jointly by multiple entities. For example, a residential community may jointly own and maintain outdoor lighting in their shared spaces such as parking areas, community parks, or recreational facilities.
  4. Utility ownership: Outdoor lighting systems may be owned and maintained by utility companies such as electric or energy companies. These companies may install and maintain street lights or other lighting systems for the public good.
  5. Third-party ownership: In some cases, a third-party entity may own and maintain outdoor lighting systems on behalf of a public or private entity. For example, a lighting contractor may install and maintain lighting in a public park on behalf of a local government.

The ownership regime of an outdoor lighting system can have implications for issues such as installation, maintenance, and cost-sharing. It is important to consider ownership when designing and implementing outdoor lighting systems to ensure their long-term effectiveness and sustainability.

More

International Commission on Illumination

National Electrical Manufacturers Association

National Electrical Contractors Association

Representative Specifications

Sam Houston State University | Division 26500 Interior and Exterior Lighting

University of Delaware | Division 265100 Interior Lighting

Cal Poly University San Luis Obispo | Division 265100 Interior Lighting

Relevant Research

Enhancing the Sustainability of Outdoor Floodlighting for Cultural Heritage Buildings

The Performance and Impact of LED Floodlights in an Outdoor Electrical Substation During Misty Weather Conditions

Replacement of HPS Luminaires with LED Luminaires for the Lighting Requirements of an Outdoor Electrical Substation

 

Halifax Coffee Shops

May 14, 2024
mike@standardsmichigan.com
, ,
No Comments

National Building Code of Canada

Dal Student Life: Our Favorite Coffee Shops

Sam Harris: Take Back Control Of Your Mind


Halifax Nova Scotia c. 1762

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nova Scotia


Rightsizing Electrical Power Systems

May 14, 2024
mike@standardsmichigan.com
, , ,
No Comments

Standards Michigan, spun-off in 2016 from the original University of Michigan Business & Finance Operation, has peppered NFPA 70 technical committees writing the 2016-2026 National Electric Code with proposals to reduce the size of building premise feeder infrastructure; accommodating the improvements made in illumination and rotating machinery energy conservation since the 1980’s (variable frequency drives, LED lighting, controls, etc.)

These proposals are routinely voted down in 12-20 member committees representing manufacturers (primarily) though local inspection authorities are complicit in overbuilding electric services because they “bill by the service panel ampere rating”.  In other words, when a municipality can charge a higher inspection fee for a 1200 ampere panel, what incentive is there to support changes to the NEC that takes that inspection fee down to 400 amperes?

The energy conservation that would result from the acceptance of our proposals into the NEC are related to the following: reduced step down transformer sizes, reduced wire and conduit sizes, reduced panelboard sizes, reduced electric room cooling systems — including the HVAC cooling systems and the ceiling plenum sheet metal carrying the waste heat away.   Up to 20 percent energy savings is in play here and all the experts around the table know it.   So much for the economic footprint of the largest non-residential building construction market in the United States — about $120 billion annually.

The market incumbents are complicit in ignoring energy conservation opportunity.  To paraphrase one of Mike Anthony’s colleagues representing electrical equipment manufacturers:

“You’re right Mike, but I am getting paid to vote against you.”

NFPA Electrical Division knows it, too.

University of Michigan

 

Rightsizing Commercial Electrical Power Systems: Review of a New Exception in NEC Section 220.12

Michael A. AnthonyJames R. Harvey

University of Michigan, Ann Arbor

Thomas L. Harman

University of Houston, Clear Lake, Texas

For decades, application of National Electrical Code (NEC) rules for sizing services, feeders and branch circuits has resulted in unused capacity in almost all occupancy classes. US Department of Energy data compiled in 1999 indicates average load on building transformers between 10 and 25 percent. More recent data gathered by the educational facilities industry has verified this claim. Recognizing that aggressive energy codes are driving energy consumption lower, and that larger than necessary transformers create larger than necessary flash hazard, the 2014 NEC will provide an exception in Section 220.12 that will permit designers to reduce transformer kVA ratings and all related components of the power delivery system. This is a conservative, incremental step in the direction of reduced load density that is limited to lighting systems. More study of feeder and branch circuit loading is necessary to inform discussion about circuit design methods in future revisions of the NEC.

CLICK HERE for complete paper

University of Houston

2026 National Electrical Code Workspace

Kindergarten

May 13, 2024
mike@standardsmichigan.com
No Comments

 

“One Hundred Children Playing in the Spring” | Su Hanchen 蘇漢臣

Safety and sustainability for any facility begins with an understanding of who shall occupy the built environment and how.  University settings, with mixed-use phenomenon arising spontaneously and temporarily, often present challenges.   Educational communities are a convergent settings for families; day care facilities among them.  First principles regarding occupancy classifications for day care facilities appear in Section 308 of the International Building Code, Institutional Group I; linked below:

Section 308 | International Building Code

The ICC Institutional Group I-4 classification includes buildings and structures occupied by more than five persons of any age who received custodial care for fewer than 24 hours per day by persons other than parents or guardian, relatives by blood, marriage or adoption, and in a place other than the home of the person cared far.  This group includes both adult and child day care.

We maintain focus on child day care.  Many educational communities operate child day care enterprises for both academic study and/or as auxiliary (university employee benefit) enterprises.

Princeton University Child Care Center

Each of the International Code Council code development groups fetch back to a shared understanding of the nature of the facility; character of its occupants and prospective usage patterns.

The Group B developmental cycle ended in December 2019.  The 2021 revision of the International Building code is in production now, though likely slowed down because of the pandemic.   Ahead of the formal, market release of the Group B tranche of titles, you can sample the safety concepts in play during this revision with an examination of the documents linked below:

2019 GROUP B PROPOSED CHANGES TO THE I-CODES ALBUQUERQUE COMMITTEE ACTION HEARINGS

2019 REPORT OF THE COMMITTEE ACTION HEARINGS ON THE 2018 EDITIONS OF THE GROUP B INTERNATIONAL CODES

Search on the terms “day care” and “daycare” to get a sample of the prevailing concepts; use of such facilities as storm shelters, for example.

“The Country School” | Winslow Homer

We encourage our safety and sustainability colleagues to participate directly in the ICC Code Development process.   We slice horizontally through the disciplinary silos (“incumbent verticals”) created by hundreds of consensus product developers every week and we can say, upon considerable authority that the ICC consensus product development environment is one of the best in the world.  Privately developed standards (for use by public agencies) is a far better way to discover and promulgate leading practice than originating technical specifics from legislative bodies.   CLICK HERE to get started.  Contact Kimberly Paarlberg (kpaarlberg@iccsafe.org) for more information.

There are competitor consensus products in this space — Chapter 18 Day-Care Occupancies in NFPA 5000 Building Construction and Safety Code, for example; a title we maintain the standing agenda of our Model Building Code teleconferences.   It is developed from a different pool of expertise under a different due process regime.   See our CALENDAR for the next online meeting; open to everyone.

 

Issue: [18-166]

Category: Architectural, Healthcare Facilities, Facility Asset Management

Colleagues: Mike Anthony, Jim Harvey, Richard Robben


Several names for this occupancy class:

  1. Nursery
  2. Crèche
  3. Playgroup
  4. Montessori
  5. Preschool
  6. Kindergarten
  7. Childcare
  8. Toddler group
  9. Daycare
  10. Early learning center

A Study of Children’s Password Practices

 

Day Care

May 13, 2024
mike@standardsmichigan.com
No Comments

2024 Complete Change Monograph (2658 Pages)

Concepts in play:

  1. tempered water for public hand-washing facilities
  2. gravity grease interceptors and gravity grease interceptors with fats, oils, and greases disposal systems.
  3. stairway walking surface treads
  4. exit signage for non-resident, non-English speaking children
  5. fire rating of corridors in schools
  6. bathing privacy concepts
  7. automatic sprinklers for pet boarding or facilities that permit animals
  8. water heater controls and monitoring; mixing valves

Link to April Committee Action Hearing Videos

“Kindergarten” c. 1885 / Johann Sperl

Safety and sustainability for any facility begins with an understanding of who shall occupy the built environment and how.  University settings, with mixed-use phenomenon arising spontaneously and temporarily, often present challenges.   Educational communities are a convergent settings for families; day care facilities among them.  First principles regarding occupancy classifications for day care facilities appear in Section 308 of the International Building Code, Institutional Group I; linked below:

2018 International Building Code Section 308 Institutional Group I-4 (Superseded in some jurisdictions)

The ICC Institutional Group I-4 classification includes buildings and structures occupied by more than five persons of any age who received custodial care for fewer than 24 hours per day by persons other than parents or guardian, relatives by blood, marriage or adoption, and in a place other than the home of the person cared far.  This group includes both adult and child day care.

We maintain focus on child day care.  Many educational communities operate child day care enterprises for both academic study and/or as auxiliary (university employee benefit) enterprises.

Princeton University Child Care Center

Each of the International Code Council code development groups fetch back to a shared understanding of the nature of the facility; character of its occupants and prospective usage patterns.

The 2024 revision of the International Building code is in production now.   Ahead of the formal, market release of the Group A tranche of titles you can sample the safety concepts in play during this revision with an examination of the documents linked below:

2019 GROUP B PROPOSED CHANGES TO THE I-CODES ALBUQUERQUE COMMITTEE ACTION HEARINGS

2019 REPORT OF THE COMMITTEE ACTION HEARINGS ON THE 2018 EDITIONS OF THE GROUP B INTERNATIONAL CODES

Search on the terms “day care” and “daycare” in the link at the top of this page to get a sample of the prevailing concepts; use of such facilities as storm shelters, for example.

“The Country School” | Winslow Homer

We encourage our safety and sustainability colleagues to participate directly in the ICC Code Development process.   We slice horizontally through the disciplinary silos (“incumbent verticals”) created by hundreds of consensus product developers every week and we can say, upon considerable authority that the ICC consensus product development environment is one of the best in the world.  Privately developed standards (for use by public agencies) is a far better way to discover and promulgate leading practice than originating technical specifics from legislative bodies.   CLICK HERE to get started.  Contact Kimberly Paarlberg (kpaarlberg@iccsafe.org) for more information.

There are competitor consensus products in this space — Chapter 18 Day-Care Occupancies in NFPA 5000 Building Construction and Safety Code, for example; a title we maintain the standing agenda of our Model Building Code teleconferences.   It is developed from a different pool of expertise under a different due process regime.   See our CALENDAR for the next online meeting; open to everyone.

 

Issue: [18-166]

Category: Architectural, Healthcare Facilities, Facility Asset Management

Colleagues: Mike Anthony, Jim Harvey, Richard Robben


LEARN MORE:

cdpACCESS Hearing Video Streaming Service

 

Life Safety Code

May 13, 2024
mike@standardsmichigan.com
,
No Comments

The Life Safety Code addresses those construction, protection, and occupancy features necessary to minimize danger to life from the effects of fire, including smoke, heat, and toxic gases created during a fire.   It is widely incorporated by reference into public safety statutes; typically coupled with the consensus products of the International Code Council.   It is a mighty document — one of the NFPA’s leading titles — so we deal with it in pieces; consulting it for decisions to be made for the following:

(1) Determination of the occupancy classification in Chapters 12 through 42.

(2) Determination of whether a building or structure is new or existing.

(3) Determination of the occupant load.

(4) Determination of the hazard of contents.

There are emergent issues — such as active shooter response, integration of life and fire safety systems on the internet of small things — and recurrent issues such as excessive rehabilitation and conformity criteria and the ever-expanding requirements for sprinklers and portable fire extinguishers with which to reckon.  It is never easy telling a safety professional paid to make a market for his product or service that it is impossible to be alive and safe.  It is even harder telling the dean of a department how much it will cost to bring the square-footage under his stewardship up to the current code.

The 2021 edition is the current edition and is accessible below:

NFPA 101 Life Safety Code Free Public Access

Public input on the 2027 Revision will be received until June 4, 2024.

 

Since the Life Safety Code is one of the most “living” of living documents — the International Building Code and the National Electric Code also move continuously — we can start anywhere and anytime and still make meaningful contributions to it.   We have been advocating in this document since the 2003 edition in which we submitted proposals for changes such as:

• A student residence facility life safety crosswalk between NFPA 101 and the International Building Code

• Refinements to Chapters 14 and 15 covering education facilities (with particular attention to door technologies)

• Identification of an ingress path for rescue and recovery personnel toward electric service equipment installations.

• Risk-informed requirement for installation of grab bars in bathing areas

• Modification of the 90-minute emergency lighting requirements rule for small buildings and for fixed interval testing

• Modification of emergency illumination fixed interval testing

• Table 7.3.1 Occupant Load revisions

• Harmonization of egress path width with European building codes

There are others.  It is typically difficult to make changes to stabilized standard though some of the concepts were integrated by the committee into other parts of the NFPA 101 in unexpected, though productive, ways.  Example transcripts of proposed 2023 revisions to the education facility chapter is linked below:

Chapter 14 Public Input Report: New Educational Occupancies

Educational and Day Care Occupancies: Second Draft Public Comments with Responses Report

Since NFPA 101 is so vast in its implications we list a few of the sections we track, and can drill into further, according to client interest:

Chapter 3: Definitions

Chapter 7: Means of Egress

Chapter 12: New Assembly Occupancies

Chapter 13: Existing Assembly Occupancies

Chapter 16 Public Input Report: New Day-Care Facilities

Chapter 17 Public Input Report: Existing Day Care Facilities

Chapter 18 Public Input Report: New Health Care Facilities

Chapter 19 Public Input Report: Existing Health Care Facilities

Chapter 28: Public Input Report: New Hotels and Dormitories

Chapter 29: Public Input Report: Existing Hotels and Dormitories

Chapter 43: Building Rehabilitation

Annex A: Explanatory Material

As always we encourage front-line staff, facility managers, subject matter experts and trade associations to participate directly in the NFPA code development process (CLICK HERE to get started)

NFPA 101 is a cross-cutting title so we maintain it on the agenda of our several colloquia —Housing, Prometheus, Security and Pathways colloquia.  See our CALENDAR for the next online meeting; open to everyone.

 

Issue: [18-90]

Category: Fire Safety, Public Safety

Colleagues: Mike Anthony, Josh Elvove, Joe DeRosier, Marcelo Hirschler

More

ARCHIVE / Life Safety Code 2003 – 2018

 


Fire and Life Safety in Stadiums

Layout mode
Predefined Skins
Custom Colors
Choose your skin color
Patterns Background
Images Background
Skip to content